Antminer Hydro Container HK3

$20.99

+ Free Shipping
ANTSPACE HK3 1030KW 210 Rack Space
Compare
Description
Specification Details For ANTSPACE HK3
Version ANTSPACE HK3
Dimensions (L*W*H) (mm) 6058*2438*2896
Miner Capacity 210 units -S19 Hyd. Series miner
Container Certification China Classification Society Certification
Safety Certification North America/StandardsNFPA 79:2021UL 508A:2018 R8.21
CSA C22.2 No. 14-18
ANSI/ISO 12100:2012
EU/Standards
EN ISO 12100EN 60204-1
Operating Power(kW) 1047~1050
PUE(Power Usage Effectiveness) 1.022(Excluding cooling tower)/1.036(Including cooling tower)
Input Voltage and Frequency 415V±5% 60Hz(North America)
400V±5% 50Hz(EU
Middle East)
Detailed Characteristics
Shipping Weight(T) 8
Operating Weight (T) 12
Main Switch of Power Distribution Cabinets(A) 1200(North America)
1250(EU
Middle East)
Rated Current(A) 952
Standard Power(kW) 1049
Maximum Power(kW) 1050
Rated Current per Miner(A) 10
Inlet Cable The inlet cables can withstand high-voltage of above 600V, with the following requirements per phase:
L1 single core cable 600kcMil(300mm²)x4
L2 single core cable 600kcMil(300mm²)x4
L3 single core cable 600kcMil(300mm²)x4
N Single-core cable 600kcMil(300mm²)x4
PE single-core cable 500kcMil(240mm²)x2
Connection Interface(Cooling Tower) DN125(GB/T 9119-2010 PN16 DN125)
Connection Interface(Plate Heat Exchage Interface) DN100(GB/T 9119-2010 PN16 DN100)
Flow Rate(m³/h) 85
Quantity of ANTSPACE powered by one 2500kVA Transformer 2
Specification Details For Dry-Wet Towers
One of the following two Dry-Wet Towers can be chosen based on the personalized demand.
Product Overview
Type Dry-Wet Tower Traditional Type DWT-T Dry-Wet Tower Container Type DWT-C
Dimensions(L*W*H)(mm) 5800*2240*4200 6058*2438*2896
Heat Dissipation Capacity(kW) 1000 1000
Outlet Temperature @ 28 Wet Bulb Temperature 35 35
Container Certification None China Classification Society Certification
Safety Certification North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21, North America/Standards: NFPA 79:2021, UL 508A:2018 R8.21,
CSA C22.2 No. 14-18, ANSI/ISO 12100:2012 CSA C22.2 No. 14-18, ANSI/ISO 12100:2012
EU Standards: EN ISO 12100, EN 60204-1 EU Standards: EN ISO 12100, EN 60204-1
Operating Power(kW) 14~28 14~28
Motor Rated Voltage and Frequency 415V±5% 60Hz(North America) 415V±5% 60Hz(North America)
400V±5% 50Hz(EUMiddle East) 400V±5% 50Hz(EUMiddle East)
Detailed Characteristics
Shipping Weight(T) 5 6
Operating WeightT 9 10
Connection Interface(Container) DN125(GB/T 9119-2010 PN16 DN125) DN125(GB/T 9119-2010 PN16 DN125)
Water Resupply Pipe Interface DN40(Internal thread) DN40(Internal thread)
Drain Pipe Interface DN65(Internal thread) DN65(Internal thread)
Noise Level @25, 16m 70dBA 70dBA
Water Consumption(m³/h) 1~1.5 1~1.5